Mechanical data | |
Design of electrical connection | Screw connection |
Conductor with strain relief | No |
Cable section | |
- Min. Cable section | |
- Max. Cable section | 1 x 1.5 mm² |
mechanical installation conditions | flush |
Switch distance | 5 mm |
Reduction factor 1 met (Y/N) | No |
Protection circuit | inductive interference protection, Protection against polarity reversal |
Pressure resistant (Y/N) | No |
Tightening torque for nuts | A/F 24 max. 1800 Ncm |
Ambient conditions | |
Ambient temperature | |
- Min. environmental temperature | −25 °C |
- Max. environmental temperature | +70 °C |
Protection class | IP67 to IEC/EN 60529 |
Electrical data | |
Design of control element | Normally open contact (NO) or Opener (NC) |
Number of wire | 3 piece |
Voltage type | DC, direct current |
Supply voltage UB | |
- Min. supply voltage | 10 V |
- Max. supply voltage | 60 V |
Switch frequency | approx. 500 Hz |
Voltage drop Ud | approx. 1.5 V (400 mA) |
Operating current Ie | 400 mA |
No-load current I0 | approx. 5.5 mA (24 V) |
Outputs | |
Design of control output | PNP |
LED switching conditions display | |
LED switching conditions display (Y/N) | Yes |
- yellow LED | |
ATEX | |
Explosion protection categories for gases | None |
Explosion protected category for dusts | None |
Dimensions | |
Dimensions of the sensor | |
- Length of sensor | 126 mm |
- Diameter of sensor | M18 |
notice | |
Instead of nuts, a mounting clamp can be provided. | |
Programmable by repositioning the plug-in jumper at the terminal screws |